Have you got a fault? Describe it in your own words.
Search the 130 technical guides: describe what happens, which component is involved and when it occurs. Find the initial checks and open the most relevant pathway.
Browse all guides
The guidance provides initial checks and does not replace the manufacturer’s instructions, a risk assessment or the competence required to work with electricity, pressure systems and refrigerants.
No results found. Try a shorter symptom, such as ‘pressure’, ‘frost’, ‘sensor’ or ‘compressor’.
Field troubleshooting
Find the next check. Not a random answer.
The search engine directs the checks; it does not confirm a cause. Identify the refrigerant, allow the system to stabilise and compare every reading with the manual and design conditions.
WIZARD / 3 STEPSFrom the symptom to the next check.
Use combinations of symptoms and SH/SC trends as guidance. For zeotropic refrigerants, use the correct dew and bubble points; for CO₂ and R290, follow the applicable procedure and use suitable instruments.
SH / SC MATRIX
The four combinations indicate a direction for further checks, not a confirmed diagnosis. Load conditions, electronic control, system type and measurement point can alter the interpretation.
HIGH SH · LOW SC
Insufficient refrigerant feed or possible leak
Observed pattern: starved evaporator, suction pressure tending to be low and potentially reduced capacity.
First action: check for leaks, verify the documented charge, confirm actual subcooling and investigate a possible restriction.
Six causes to distinguish. Before replacing components.
The guides put the initial checks in order. Stop and refer to the specific manual before working on electrical systems, pressure systems, flammable refrigerants or transcritical CO₂.
CRITICALNon-condensable gases in the system⌄
Why it can happen
Air or other non-condensable gases take up space in the condenser and can raise condensing pressure above that expected for the operating conditions.
Before touching any valves
Check ambient temperature, air or water flow and condenser cleanliness.
Record pressure, saturation temperature and liquid-line temperature.
Do not vent refrigerant or alter the charge: recovery and the applicable procedure are mandatory.
Technical check
Allow the system to stabilise; first rule out inadequate heat transfer and overcharge. Then compare the readings with the P/T chart for the correct refrigerant and the manufacturer’s manual.
Inspect vibration points, valves, brazed joints and oil traces.
Use a leak-detection method compatible with the refrigerant and the environment.
Technical check
High SH and low SC are a possible trend, not confirmation. Isolate, test and repair in accordance with the procedure; avoid repeated topping up without locating the cause.
Measure the temperature upstream and downstream of the component using a stable reference point.
Check the solenoid command and electrical state, where fitted.
Compare with the liquid-line diagram.
Technical check
A restriction can retain liquid upstream and starve the evaporator. Follow the measurement sequence and the manual; do not compensate by adjusting the expansion valve.
MODERATEDirty condenser or restricted heat transfer⌄
Before touching any valves
Check the fans, direction of rotation and hot-air recirculation.
Measure inlet and outlet air temperatures and condensing pressure.
Check fins, filters and unobstructed airflow.
Technical check
An air-side or water-side fault can resemble a refrigerant charge problem. Restore correct heat transfer and reassess the readings only after the system has stabilised.
CRITICALLiquid refrigerant returning to the compressor⌄
Priority
Possible liquid slugging, oil foaming or an abnormally cold suction line require caution: do not pursue display-case performance at the expense of the compressor.
Before touching any valves
Check defrost operation, fans and frost distribution.
Measure SH at the point specified by the manufacturer.
Check the valve or sensor, suction accumulator and restart sequence.
Technical check
The cause may be control, frost, the bulb or sensor, or a transient condition. Assess behaviour over a complete cycle and refer to the compressor manual.
DETECTORThermal protection or pressure switch tripped⌄
Before resetting
Record the code, time and system status.
Compare an independent measurement with the device setting.
Check the control chain, voltage and refrigeration operating conditions.
Technical check
Do not bypass the device or raise its settings to keep the system running. Identify the primary cause: heat transfer, load, voltage, current or actual pressure.
Checks on electrical parts, pressurised systems and refrigerants must be carried out by trained and authorised personnel using suitable instruments, personal protective equipment, current manuals and applicable procedures.