Transparent calculations, alarms for model and schemes to carry on the field. Start from your machine data, keep the measurements and open the source when needed.

01 / CALCOLO A REGIME

How much do you lose along the line?

Synusoidal AC line, single-phase or three-phase balanced, inductive load. Insert resistance and rectifier for conductor from the cable manufacturer, to the operating temperature. Not applicable to the PWM output of a Drives, in point or to unbalanced loads.

Enter all the data to start.
Formula and source

ΔU = k × I × L/1000 × (R × cos φ + X × √(1 − cos2 φ)); k = 2 in monophase, √3 in triphase. Percentage = 100 × ΔU / U. It is the only route: add the fall upstream for the total. No universal regulatory threshold is applied.

Schneider Electric · Electrical Installation Practical guides
02 / VERIFICATION PRELIMINING

Protection and line are consistent?

Check of three numerical conditions for a switch that also protects from overload. Do not choose the compressor's curve or magnetothermic. For separate overload protection, fuse or Drives, use the manufacturer's specific coordination.

The result is not executive dimensioning.

Please note: start-up and time-current curve, coordination with contact and overload, passing energy, interruption times, selectivity, differential protection where required and OEM requirements. Break data related to correct voltage and device standard.

Source · Ib ≤ In ≤ Iz and power of interruption di
03 / EXACT CODE

Alarm & fault codes for instrument

Search for an alarm code →

An initial selection of 25 documented codes. Also transcribe variant and machine revision. The meaning of the code directs the verification: it does not show which component to replace.

The tabs are collected below; choose the template to filter.

Dixell

P1 · temperature probe environment

Check connection and temperature probe before replacing it.

1592020060 · r1.1 · 27/04/2015 · §14

Official manual e
Dixell

P2 · Anomaly temperature probe evaporator

temperature probe verification and connection; end frost passes on time.

1592020060 · r1.1 · 27/04/2015 · §14

Official manual e
Dixell

HA · High temperature alarm

Compare independent measurement, cell threshold and conditions.

1592020060 · r1.1 · 27/04/2015 · §14

Official manual e
Dixell

LA · Low temperature alarm

Compare independent measurement and configured threshold.

1592020060 · r1.1 · 27/04/2015 · §14

Official manual e
Dixell

CA · Severe external alarm or pressure switch

Distinguish i1F=bAL from i1F=PAL. The outputs are disabled: identifies the permissive intervened.

1592020060 · r1.1 · 27/04/2015 · §14

Official manual e
Danfoss ERC 21X

E29 · Anomaly temperature probe air

Check temperature probe Sair and connection.

BC194286421698en-001101 · 09/2025 · table 38

Official manual e
Danfoss ERC 21X

E27 · Anomaly temperature probe evaporator

temperature probe S5 and connection.

BC194286421698en-001101 · 09/2025 · table 38

Official manual e
Danfoss ERC 21X

E30 · Anomaly temperature probe capacitor

temperature probe Sc and connection.

BC194286421698en-001101 · 09/2025 · table 38

Official manual e
Danfoss ERC 21X

A01 · High cold-room temperature

Compare reading, threshold and real conditions.

BC194286421698en-001101 · 09/2025 · table 38

Official manual e
Danfoss ERC 21X

A02 · Low cold-room temperature

Compare reading, threshold and real conditions.

BC194286421698en-001101 · 09/2025 · table 38

Official manual e
Danfoss ERC 21X

A99 · High Power Voltage

Record voltage and moment of the disturbance.

BC194286421698en-001101 · 09/2025 · table 38

Official manual e
Danfoss ERC 21X

AA1 · Low Power Voltage

Record voltage and moment of the disturbance.

BC194286421698en-001101 · 09/2025 · table 38

Official manual e
Danfoss ERC 21X

A61 · High condenser temperature

Check air flow and measure.

BC194286421698en-001101 · 09/2025 · table 38

Official manual e
CAREL UltraCella

rE · Anomaly temperature probe virtual adjustment

Identify probes and configuration that make up the adjustment value.

+0300083EN · document version 1.14 · §8.8

Official manual e
CAREL UltraCella

E0 · temperature probe B1

temperature probe verification and connection associated with B1.

+0300083EN · document version 1.14 · §8.8

Official manual e
CAREL UltraCella

E1 · Anomaly temperature probe B2

Configured function check and B2 connection.

+0300083EN · document version 1.14 · §8.8

Official manual e
CAREL UltraCella

HI · High temperature alarm

Compare independent measurement and set threshold.

+0300083EN · document version 1.14 · §8.8

Official manual e
CAREL UltraCella

LO · Low temperature alarm

Compare independent measurement and set threshold.

+0300083EN · document version 1.14 · §8.8

Official manual e
CAREL UltraCella

Pd · Maximum pump-down time

Collect pressure and command sequence trend; do not increase time without diagnosis.

+0300083EN · document version 1.14 · §8.8

Official manual e
CAREL ir33 (refrigeration)

E0 · temperature probe environment S1

temperature probe type verification, connection and measurement according to the variant.

+030220441 · alarm table §8.1 · not ir33 Universal

Official manual e

If the code is not present, do not use that of another family. Search the exact manual in Manual library →

Sources consulted on 10 September 2026. Independent portal, not official assistance of the brands.

04 / EXCHANGE

Three tables, even without cover.

Functional diagrams for refrigeration

Direct start, control and permissive, compressor with Drives. Horizontal A4 vector PDF, 3 pages: text and lines remain sharp even enlargement.

Non-executive functional references: no universal clamps or calibrations. To wire, you need the schematic of the machine and manuals of the installed variant.

Download PDF · 3 tables

Save the file in File / Download and open it once before entering the cell. The external manuals are not automatically saved: download also those of your model.