Danfoss · FC 103Return oil at low speed
How to read the Oil Return Management function without transferring times and frequencies from one compressor to another.
Verified fieldFC 103 · parameters 28-10...28-16 · approved OEM application
SEQUENZA DI LETTURAControls in order
- Confirm in the compressor document the minimum speed continues and the operating field allowed.
- Record time under the minimum speed, history of events and real conditions of the refrigerator circuit.
- Compare activation, boost speed, duration and range of function 28-10...28-16 with machine design.
- Check that the boost does not cause unwanted staging or destaging in the pack controller.