REFTHEREFRIGERATION TECHNOLOGY
TECHNOLOGY REFTHE · SCHEDA 16
CDS 803 · 6–30 kW · compatible software

CDS 803: from code to targeted verification

The CDS 803 distinguishes warning, alarm and triple locked. Each code must be connected to size, software, compressor status and electrical conditions before reset.

Family
CDS 803 · 6–30 kW · compatible software
Code or symptom
4 · 7 · 8 · 9 · 10 · 13 · 14 · 16 · 17 · 18 · 30 · 31 · 32 · 69 · 99
Topic
Compressor diagnostics
Objective
Demonstrate the cause before changing parameters or replacing components.
SINTESI

The case in 60 seconds

What does it mean?

The CDS 803 distinguishes warning, alarm and triple locked. Each code must be connected to size, software, compressor status and electrical conditions before reset.

First data to be stored

Transcribe code, status, power 6–10 or 18–30 kW, software version and time of the cycle in which it appears.

Diagnosis

The code or symptom directs research, but does not show the fault component alone.

METODO

Diagnostic map

Follow the rows in order. Each phase must produce evidence before moving to the next.

PhaseControlsEvidence to obtainNext decision
01Recognize and collect
  • Transcribe code, status, power 6–10 or 18–30 kW, software version and time of the cycle in which it appears.
  • Keep compressor data, speed reference and last events without enabling the autoreset.
Event context and complete initial data.If a data is missing, do not reset to attempts: complete the initial picture first.
02Check and separate hypotheses
  • Follow the official table: separates network/DC bus, load and temperature, overcurrent, land/race, control word, start failed and motor phases.
  • For 18 or 99 verify that the rotor can move and that selection and engine data are consistent; do not transform the phrase “Check fan resistance” into an undefined test.
External causes, configuration, circuit and separate process.If the data does not match, return to the correct schema and revision before changing parameters.
03Interpret and demonstrate
  • Compare the code with the parameters mentioned by Programming Practical guides and the limits of the compressor approved by OEM.
  • After correction, run a controlled start, recording current, frequency, pressure and process response.
Cause supported by repeatable data and authorized evidence.If the cause is not proven, stop changes and involve manufacturer, OEM or machine manager.
CAPITOLO 01

Reading and observation

Recognize and collect

  1. Transcribe code, status, power 6–10 or 18–30 kW, software version and time of the cycle in which it appears.
  2. Keep compressor data, speed reference and last events without enabling the autoreset.
Result of the chapter

Event context and complete initial data.

If the result does not match

If a data is missing, do not reset to attempts: complete the initial picture first.

CAPITOLO 02

Qualified technician

Check and separate hypotheses

  1. Follow the official table: separates network/DC bus, load and temperature, overcurrent, land/race, control word, start failed and motor phases.
  2. For 18 or 99 verify that the rotor can move and that selection and engine data are consistent; do not transform the phrase “Check fan resistance” into an undefined test.
Result of the chapter

External causes, configuration, circuit and separate process.

If the result does not match

If the data does not match, return to the correct schema and revision before changing parameters.

CAPITOLO 03

Specialist deepening

Interpret and demonstrate

  1. Compare the code with the parameters mentioned by Programming Practical guides and the limits of the compressor approved by OEM.
  2. After correction, run a controlled start, recording current, frequency, pressure and process response.
Result of the chapter

Cause supported by repeatable data and authorized evidence.

If the result does not match

If the cause is not proven, stop changes and involve manufacturer, OEM or machine manager.

ERRORI FREQUENTI

What to avoid

  • Use repeated resets as a diagnostic test.
  • Transfer codes, thresholds or parameters from one Drives family to another.
  • Change a protection before connecting symptoms, measurement and phase of the cycle.
  • The authorset can produce an unexpected start. Only qualified personnel: stop, disconnect all sources, wait for the expected download and check with appropriate tool.
COLLAUDO

When the problem is really solved

The code remains absent in the reproduced cycle, the cause is demonstrated and the electric and cold quantities fall within the limits of the machine and compressor.

  • The cause is supported by data and not only by the momentary absence of the alarm.
  • The cycle that generated the problem has been repeated in authorized conditions.
  • Final configuration, measurements and outcome are consistent with applicable machine, drive and documentation.
PRIMARY SOURCES

Applicable documents

Always check size, firmware, options and revision. These sources do not extend the case to other families.