USF: insufficient power supply or transient decrease

ATV320 signals too low network voltage or a transient fall. It is necessary to distinguish the plant event from an internal condition before changing thresholds.

Family
ATV320 · USF · FAQ and manual of the installed revision
Code or symptom
USF · USb-
Topic
Power supply
Objective
Demonstrate the cause before changing parameters or replacing components.
SINTESI

The case in 60 seconds

What does it mean?

ATV320 signals too low network voltage or a transient fall. It is necessary to distinguish the plant event from an internal condition before changing thresholds.

First data to be stored

Record cycle phase, code, nominal voltage and loads that enter into service at the same time.

Diagnosis

The code or symptom directs research, but does not show the fault component alone.

METODO

Diagnostic map

Follow the rows in order. Each phase must produce evidence before moving to the next.

PhaseControlsEvidence to obtainNext decision
01Recognize and collect
  • Record cycle phase, code, nominal voltage and loads that enter into service at the same time.
  • Check license plate and history without canceling the event or modifying UNDERVOLTAGE MGT.
Event context and complete initial data.If a data is missing, do not reset to attempts: complete the initial picture first.
02Check and separate hypotheses
  • Qualified staff: measure the voltages chained in input with appropriate CAT tool and compares imbalance and fall under load.
  • Follow the DC bus control manual to the PA/PC points and compare the parameters of the USb- menu with the project.
External causes, configuration, circuit and separate process.If the data does not match, return to the correct schema and revision before changing parameters.
03Interpret and demonstrate
  • Correct the event with network, protections, contactors, section of the cables and transients registered; avoids conclusions from a single vacuum measure.
  • After correction repeat the cycle monitored and verify that tension, current and process remain stable.
Cause supported by repeatable data and authorized evidence.If the cause is not proven, stop changes and involve manufacturer, OEM or machine manager.
CAPITOLO 01

Reading and observation

Recognize and collect

  1. Record cycle phase, code, nominal voltage and loads that enter into service at the same time.
  2. Check license plate and history without canceling the event or modifying UNDERVOLTAGE MGT.
Result of the chapter

Event context and complete initial data.

If the result does not match

If a data is missing, do not reset to attempts: complete the initial picture first.

CAPITOLO 02

Qualified technician

Check and separate hypotheses

  1. Qualified staff: measure the voltages chained in input with appropriate CAT tool and compares imbalance and fall under load.
  2. Follow the DC bus control manual to the PA/PC points and compare the parameters of the USb- menu with the project.
Result of the chapter

External causes, configuration, circuit and separate process.

If the result does not match

If the data does not match, return to the correct schema and revision before changing parameters.

CAPITOLO 03

Specialist deepening

Interpret and demonstrate

  1. Correct the event with network, protections, contactors, section of the cables and transients registered; avoids conclusions from a single vacuum measure.
  2. After correction repeat the cycle monitored and verify that tension, current and process remain stable.
Result of the chapter

Cause supported by repeatable data and authorized evidence.

If the result does not match

If the cause is not proven, stop changes and involve manufacturer, OEM or machine manager.

ERRORI FREQUENTI

What to avoid

  • Use repeated resets as a diagnostic test.
  • Transfer codes, thresholds or parameters from one Drives family to another.
  • Change a protection before connecting symptoms, measurement and phase of the cycle.
  • PA/PC points are not “safe points”. Internal measures only by qualified personnel, with LOTO procedure, download time and manual size.
COLLAUDO

When the problem is really solved

The cause of the fall is proven and correct, tensions remain within specification during the real cycle and USF does not recompense.

  • The cause is supported by data and not only by the momentary absence of the alarm.
  • The cycle that generated the problem has been repeated in authorized conditions.
  • Final configuration, measurements and outcome are consistent with applicable machine, drive and documentation.
PRIMARY SOURCES

Applicable documents