ACH580 ready but not part: permissive and interlock

The codes indicate run enable, run permissive or start interlock missing: the drive can be healthy but correctly blocked by the logic machine.

Family
ACH580 · HVAC program · hexadecimal codes
Code or symptom
AFEB · AFED · AFEE · AFEF · AFF0 · AFF1
Topic
Command and permissive
Objective
Demonstrate the cause before changing parameters or replacing components.
SINTESI

The case in 60 seconds

What does it mean?

The codes indicate run enable, run permissive or start interlock missing: the drive can be healthy but correctly blocked by the logic machine.

First data to be stored

It records hexadecimal code, command source, local/remote state and cycle phase.

Diagnosis

The code or symptom directs research, but does not show the fault component alone.

METODO

Diagnostic map

Follow the rows in order. Each phase must produce evidence before moving to the next.

PhaseControlsEvidence to obtainNext decision
01Recognize and collect
  • It records hexadecimal code, command source, local/remote state and cycle phase.
  • Recovers the scheme and locates the external permissive or fieldbus provided without piercing it.
Event context and complete initial data.If a data is missing, do not reset to attempts: complete the initial picture first.
02Check and separate hypotheses
  • For AFEB test source and parameter status 20.12; for AFED use 20.40; for AFEE–AFF1 compares 20.41–20.44 with real inputs.
  • Check signal, power, wiring and master status while keeping intact STO and interlocking.
External causes, configuration, circuit and separate process.If the data does not match, return to the correct schema and revision before changing parameters.
03Interpret and demonstrate
  • Compare state words and PLC/BMS logic with saved configuration and behavior required by the project.
  • Perform only one supervised test after showing that machine and process can leave safely.
Cause supported by repeatable data and authorized evidence.If the cause is not proven, stop changes and involve manufacturer, OEM or machine manager.
CAPITOLO 01

Reading and observation

Recognize and collect

  1. It records hexadecimal code, command source, local/remote state and cycle phase.
  2. Recovers the scheme and locates the external permissive or fieldbus provided without piercing it.
Result of the chapter

Event context and complete initial data.

If the result does not match

If a data is missing, do not reset to attempts: complete the initial picture first.

CAPITOLO 02

Qualified technician

Check and separate hypotheses

  1. For AFEB test source and parameter status 20.12; for AFED use 20.40; for AFEE–AFF1 compares 20.41–20.44 with real inputs.
  2. Check signal, power, wiring and master status while keeping intact STO and interlocking.
Result of the chapter

External causes, configuration, circuit and separate process.

If the result does not match

If the data does not match, return to the correct schema and revision before changing parameters.

CAPITOLO 03

Specialist deepening

Interpret and demonstrate

  1. Compare state words and PLC/BMS logic with saved configuration and behavior required by the project.
  2. Perform only one supervised test after showing that machine and process can leave safely.
Result of the chapter

Cause supported by repeatable data and authorized evidence.

If the result does not match

If the cause is not proven, stop changes and involve manufacturer, OEM or machine manager.

ERRORI FREQUENTI

What to avoid

  • Use repeated resets as a diagnostic test.
  • Transfer codes, thresholds or parameters from one Drives family to another.
  • Change a protection before connecting symptoms, measurement and phase of the cycle.
  • Do not bridge consensus, permissive, interlocking or STO. If it is not clear the function of an input, stop and consult schema, OEM or security manager.
COLLAUDO

When the problem is really solved

The permissive comes back for the intended cause, the drive only leaves in the authorized sequence and the correction is also confirmed by the supervision system.

  • The cause is supported by data and not only by the momentary absence of the alarm.
  • The cycle that generated the problem has been repeated in authorized conditions.
  • Final configuration, measurements and outcome are consistent with applicable machine, drive and documentation.
PRIMARY SOURCES

Applicable documents

Always check size, firmware, options and revision. These sources do not extend the case to other families.